12.2 The top of the flue must be capped with an appropriate anti down draft cowl.
Note: As per national standards, the finished terminal must be in clear air and not enclosed
in any way.
All the required flue components are available from your Escea dealer in both kitset form
and as individual components.
LONG SECTION THROUGH FLUE ENCLOSURE
Angle fixing bracket
supplied with flue kit
Seal - Deck Tight or similar
600mm clearance to nearest part of roof
Gap between flue shield and any timber
Trimmers shown diagrammatic
GENERAL CONSTRUCTION AND CLADDING SHOWN AND IS INDICATIVE ONLY
ALL INSTALLATION & FLUING MUST COMPLY WITH NZS 5261
150
100
25
gap between flue shield and any timber
LONG SECTION THROUGH FLUE ENCLOSURE
Scale: NTS
200 min but allow for flue flashings at base
trimmers shown
diagrammatic
25
if another flue
shares same
enclosure
ENCLOSURE DESIGN EXAMPLE ONLY
GENERAL CONSTRUCTION AND
CLADDING SHOWN INDICATIVE ONLY
deck-tite or
similar flashing
angle fixing
bracket supplied
with flue kit
200mm min