Escea IB600 Installation Manual Page 8

  • Download
  • Add to my manuals
  • Print
  • Page
    / 48
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 7
630184_4 IB Installation Manual NZ
8
IB850 & IB1100:
Therefore excess = 43MJ/hr - 25.2MJ/hr = 17.8MJ/hr = 4.94kW
Wall Vent Opening = 4.94 x 500mm
2
= 2470mm
2
IB600:
Therefore excess = 36MJ/hr - 25.2MJ/hr = 10.8MJ/hr = 3kW
Wall Vent Opening = 3 x 500mm
2
= 1500mm
2
This is the minimum recommended wall vent required over and above any existing
adventitious ventilation.
4.0 Cavity Base:
This appliance MUST be fully supported on its base. The base must extend over the entire
area of the underside of the appliance. The base must also be levelled to prevent vibration
from possible fan imbalance. For the installation of an IB1100 the base of the cavity must be
strong enough to support the total product weight, which is a minimum of 70kg.
The base of the product must be fully supported at either side and at the centre front to
back.
5.0 Hearth:
If this fire is being installed at floor level a hearth made from non-combustible material must
extend no less that 300mm from the front of the fire. This hearth should be at least as wide
as the fire‟s outer fascia and no less than 10mm thick. Raised hearths can be any size but
must also be constructed from non combustible materials.
5.1 The floor in front of this hearth will still get warm so if the floor covering is vinyl, nylon carpet
or another heat sensitive material then we recommend extending the hearth to 450mm from
the fire.
5.2 NOTE: If the hearth is to be covered with tiles or some other veneer then the fire must be
installed so that the base of the „Zero Clearance Kit‟ is level with the finished top surface of
the hearth.
6.0 Raised Installations Up a Wall:
If the fire is being located in such a way that the bottom of the cavity is any more than
100mm up off the ground no hearth is required. Escea recommend that if a heater is being
mounted more than 100mm up a blank wall and no hearth is being used, then a four sided
fascia is used (available from your Escea dealer).
7.0 Wall Linings: The front mounting flanges of the „Zero Clearance Kit‟ MUST be on top of the
FINISHED wall surface in order for the fascia panels to mount properly. Take into account
any plaster board, tiles or any other finishing surface that may be intended for the finished
wall surface. Wall finishing materials must not encroach upon the minimum cavity
clearances given in section 1.0. The wall board that lines the outside of this opening can be
normal dry wall (plaster board) and does not need to be non-combustible.
Note: The temperature of the wall lining directly above the heater does get warm and hence
may discolour paint finishes that are susceptible to temperature damage or distort vinyl wall
coverings. For durability of finishes and surfaces you should contact the relevant
manufacturer for their specification.
Page view 7
1 2 3 4 5 6 7 8 9 10 11 12 13 ... 47 48

Comments to this Manuals

No comments